●Indoor air changes: Class 100,000 10-15 times/hour; Class 10,000 15-25 times/hour; Class 1,000 50-52 times/hour;
●Average wind speed of Class 100 operating point section 0.25-0.35m/s. Indoor noise: ≤ 65dB (A);
●Indoor pressure difference: high clean room area for adjacent low clean room area ≥ 5Pa, to non-clean room area ≥ 10Pa;
●Indoor temperature: Winter :16℃± 2℃; (room temperature);
●Indoor relative humidity: 45-65% (RH); (Special requirements);
●Indoor noise: ≤ 60dB (A);
●Indoor illumination: ≥ 300Lux; fresh air volume: 20% -30% of the total air supply.